Products

FireHalt® Fire Protection Products

Downlighter Covers

FireHalt® Downlighter covers have been developed to provide maximum protection for holes created by the introduction of a downlighter and to allow for ease of fitting. In a fire situation, the cover expands internally to fill all the available space with a fire resistant, highly insulating char.

The fire is unable to penetrate the hole and the cover gives additional insulation protection to the ceiling void by reducing the possibility of heat build up and ignition of flammables, such as accumulated dust and insulation.

Before Fire (cut away section)

After Fire (cut away section)

Key Features

Cover is Flexible and Lightweight and can be fitted from below or above the ceiling.

Cover is ventilated to reduce heat build up in the light fitting.

Simple fixing method; can be fitted in seconds.

No screws, drilling or support required.

Can be used in suspended plasterboard and concrete ceilings.

Cost effective

Covers a wide range of mains and low voltage downlighters.

For thirty and 60 minute fire rated ceilings.

Prevents fire from penetrating the ceiling void and retains ceiling’s fire protection integrity.

When exposed to fire it provides a highly insulating, stable char.

Unaffected by moisture, and none toxic.

Once it is installed it is free from additional maintenance.

Once fitted, downlighter can be installed as normal

Sizes Available

O/D

Height

Cut-out Size

150

150

50 to 75

200

200

75 to 100

250

250

100 to 140

 
Test Data 1:

FireHalt® Downlighter covers underwent a fire resistance test in a suspended ceiling employing the general procedures and criteria of BS476 Part 23:1987

Date of test: 5th August 1999

Duration of effective protection: 72 minutes (No Failure)

Certificate No.: FEI/F99029

Test House: Chiltern International Fire

Test Data 2:

FireHalt® Downlighter covers underwent a fire resistance test in a plasterboard ceiling employing the general procedures and criteria of BS EN 1365-2:2000

Date of test: 18th April 2000

Integrity reached: 60 minutes (No Failure)

Insulation Reached: 60 minutes (No Failure)

Certificate No.: TE94667 Test House: BRE

 

 